| Phase: | Three Phase | 
| Type: | On-line | 
Suppliers with verified business licenses
 
     
     
     
     Specification
Specification
  | General | ||||||||
| UPS output power rating (1.0 p.f.) | 25,50,75,100,125,150,175,200kW | |||||||
| Efficiency in double conversion mode | >96% | |||||||
| Efficiency in Energy Saver System (ESS) | >99% | |||||||
| Static bypass rating | 200kW | |||||||
| External paralleling | up to 4 units with HotSync technology | |||||||
| UPS topology | Double conversion | |||||||
| UPS degree of protection | IP20 | |||||||
| Acoustic noise at 1 m,in 25 ºC ambient temperature | <70 dBA in double conversion,<55 dBA in ESS | |||||||
| Altitude (max) | 1000m above sea level at 40 ºC.Maximum 2000m with 1%derating per each add.100 m | |||||||
| Input | ||||||||
| Rated input voltage | 220/380 V,230/400 V,240/415V 50/60 Hz | |||||||
| Voltage tolerance -Rectifier input | 187 to 276V | |||||||
| Voltage tolerance -Bypass input | Rated voltage -15%/+10% | |||||||
| Rated input frequency | 50 or 60 Hz,user configurable | |||||||
| Frequency tolerance | 40 to 72 Hz | |||||||
| Input wiring | 3 phase+neutral | |||||||
| Input power factor at 100%load | >0.99 | |||||||
| Input ITHD | <3% | |||||||
| Rated input r.m.s current | 25kW | 50kW | 75kW | 100kW | 125kW | 150kW | 175kW | 200kW | 
| 380V | 40A | 80 A | 120A | 159 A | 199 A | 239A | 278 A | 318 A | 
| 400V | 38A | 76A | 114 A | 51 A | 189 A | 227 A | 264 A | 302 A | 
| 415V | 37 A | 73 A | 110 A | 46 A | 182 A | 219 A | 255 A | 291 A | 
| Soft start capability | Yes | |||||||
| Intemal backfeed protection | Yes | |||||||
| Output | ||||||||
| Output wiring | 3 phase +neutral | |||||||
| Rated output voltage rating | 220/380 V,230/400 V,240/415 V.configurable | |||||||
| Total voltage harmonic distortion | <1%(100%linear load);<3%(100%non-linear load) | |||||||
| Output power factor | 1.0 | |||||||
| Permitted load power factor | 0.8 lagging to 0.8 leading | |||||||
| Overload on inverter | 10 min 102-110%,60 sec 111-125%,10 sec 126-150%,300 ms>150% | |||||||
| Overload on bypass | Continuous<125%,20 ms 1000% | |||||||
| Battery | ||||||||
| Battery type | 12V,VRLA | |||||||
| Charging method | ABM technology or Float | |||||||
| Temperature compensation | Optional | |||||||
| Battery nominal voltage (VRLA) | 480V | |||||||
| Battery quantity | 36 to 44 blocks.Default is 40 blocks | |||||||
| Charge current limit | Default 5A,configurable maximum 25A per UPM | |||||||
| Battery start capability | Yes | |||||||
| Communications | ||||||||
| Minislot | 3 communication bays | |||||||
| Network/SNMP interface | Yes,optional | |||||||
| Serial ports | Built-in host and device USB | |||||||
| Standard connectivity ports | Mini-slot ports for optional cards,Device USB and Host USB,RS-232 service port,relay output, 5 building alarm inputs and a dedicated EPO | |||||||
| Accessorles | MiniSlot connectivity (Web/SNMP,ModBus/Jbus,Relay) | |||||||
| External Battery Cabinet(EBC) | ||||||||
| Parallel Tie Cabinet(PTC) | ||||||||
| External Maintenance Bypass Switches(EMBS) | ||||||||
| External Battery Cabinet Breaker(EBCB) | ||||||||
| Compliance with standards | ||||||||
| Safety | IFC 62040-1 | |||||||
| EMC | EC 62040-2 | |||||||
| Performance | EC 62040-3 | |||||||