                                            Still deciding? Get samples of $ !
                                            
                                         
                                                                                    Request Sample
                                                                             | 
                            
| Customization: | Available | 
|---|---|
| After-sales Service: | Yes | 
| Type: | Cabinet Air Conditioner | 
Suppliers with verified business licenses







Technical Parameters  | |||||||
ParametersP1035P1045P1050P1060P2070  | |||||||
Dimensions(W×D×H)(mm)  | 1330×995×1975  | 2430×995×1975  | |||||
Operational Weight(kg)  | 425  | 430  | 460  | 465  | 750  | ||
Test condition &Loading:RAT 35C/26%RH,Condensing temp 45℃&100%loading  | |||||||
Net Sensible Cooling Capacity(kW)*  | 39.7  | 46.2  | 51.1  | 61.4  | 73.0  | ||
AirFlow(m³/h)  | 13000  | 13500  | 14200  | 14200  | 14800  | ||
Power Consumption(KW)  | 20.4  | 22.8  | 28.9  | 34.8  | 41.1  | ||
EC Fan ESP(Pa)  | Available ESP:50~200;Standard for down flow:50Pa &up flow:50P  | ||||||
Type of filter  | Dry media type(EU4/MERV8 rating)  | ||||||
Electrical Characteristics  | 380V~415V 3P+N;50Hz/60Hz  | ||||||
Parameters  | P2080  | P2090  | P2100  | P2110  | P2120  | ||
Dimensions(W×D×H)(mm)2430×995×1975  | |||||||
Operational Weight(kg)  | 755  | 760  | 780  | 785  | 790  | ||
Test condition &Loading:RAT 35℃/26%RH,Condensing temp 45℃&100%loading  | |||||||
Net Sensible Cooling Capacity(kW)*  | 81.6  | 92.4  | 101.8  | 112.3  | 123.2  | ||
AirFlow(m³/h)  | 16900  | 19000  | 21200  | 22350  | 24400  | ||
Power Consumption(KW)  | 42.4  | 45.6  | 46.2  | 47.7  | 49.9  | ||
EC Fan(ESP)(Pa)  | Available ESP:50~200;Standard for down flow:50Pa &up flow:50Pa  | ||||||
Type of filter  | Dry media type(EU4/MERV8 rating)  | ||||||
Electrical Characteristics  | 380V~415V;3P+N;50Hz/60Hz  | ||||||