| Nominal Ratings (kVA/kW) |
100 kVA |
120 kVA |
160 kVA |
200 kVA |
250 kVA |
| |
| Input |
|
| Nominal input voltage (V) |
380 / 400 / 415 (three-phase and sharing neutral with the bypass input) |
| Input voltage range without battery discharge (V)* |
228 to 478 |
| Nominal input frequency (Hz) |
50 / 60 |
| Input frequency range (Hz) |
40 to 70 |
| Bypass voltage tolerance (%) |
Upper limit: +10, +15, or +20, default: +15 |
| Lower limit: -10, -20, -30, -40, default: -20 |
| Bypass frequency tolerance (%) |
±10 |
| Input power factor (kW/kVA) |
0.99 |
| Input THDi* |
<3% (full load), 4% (half load) |
| Battery |
|
| Battery bus voltage (VDC) |
360 to 528 , 2 Wire |
| Battery charger max. (A) |
30 |
45 |
45 |
60 |
75 |
| Output |
|
| Nominal output voltage (V) |
380 / 400 / 415 (three-phase and sharing neutral with the bypass input) |
| Nominal output frequency (Hz) |
50 / 60 |
| Nominal active power (kW) |
100 |
120 |
160 |
200 |
250 |
| THDv with 100% linear load (%) |
1 |
| Inverter overload capacity |
<105 % for Continuous; <110% for 60min; <125 % 10 min; <150 % for 1 min; >150 % for 200ms |
| Efficiency |
|
| Double conversion mode |
Up to 97% |
| Dynamic online mode |
Up to 98.8% |
| Eco mode |
Up to 99.2% |
| Dimensions and weight |
|
| Dimensions (W x D x H), mm |
600 x 850 x 1600 |
600 x 850 x 2000 |
| Shipping dimensions (W x D x H), mm |
800 x 1000 x 1800 |
800 x 1000 x 2180 |
| Weight, kg |
315 |
350 |
350 |
412 |
447 |
| Shipping weight, kg |
345 |
380 |
380 |
443 |
478 |
| General |
|
| Noise at 1 m dBA |
60 |
|
|
62 |
|
| Altitude |
1500 m no derating, 1500 to 3000 m derate power by 1 % per each 100 m increase |
| Protection level |
IP20 (IP21, IP31 optional) |
| General and safety requirements for UPS |
IEC 62040-1 |
| EMC requirements for UPS |
IEC 62040-2 |
| UPS classification according to IEC EN 62040-3 |
VFI-SS-111 |
| CPSS applications |
EN 50171 |
| Rail applications |
EN 50121-1; EN 50121-5 |