Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Rated power | 25KVA | 300 kVA 400KVA 500KVA |
Input | ||
Rated input voltage (V) | 380/400/415,3Ph+N+PE | |
Input voltage range (V) | 228~476,-20%~+25%full load operation,-20%~-40%derating to 70%rated load | |
Rated operating frequency(Hz) | 50/60 | |
nput frequency range(Hz) | 40~70 | |
Bypass voltage range(%) | Upper limit:+10,+15 or+20,default value:+15 Lower limit: | |
-10,-20,-30,-40,default value:-20 | ||
Bypass frequency range (%) | ±10 | |
Input power factor | >0.99 | |
Enter THDi | <3%(100%non-linear load) | |
Battery | ||
Rated battery bus voltage (VDC) | 480 | |
Supported battery types | Lithium-ion batteries,lead-acid valve-regulated batteries | |
Output | ||
Rated output voltage(V) | 380/400/415,3Ph+N+PE | |
Rated output frequency(Hz | 50/60 | |
Output power factor | 1 | |
Inverter overload capability | 105%continuous;110%for60min; 125%for 10min; 150%for lmin; | |
Efficiency | ||
Double conversion mode | Up to 97.5% | |
Dynamic online mode | Up to 99% | |
Size | ||
Size(W*D*Hmm) | 600*850*2000 | 600*1000*2000 |
Working environmen | ||
Noise dB(A)at lm | 68 | |
Altitude | No derating for 1500 m,derating required for 1500-3000 m,and 1%derating for every 100 m increase in altitude | |
IP protection leve | IP20 | |
Standards compliant | Safety regulations:IEC 62040-1,electromagnetic compatibility:ICE 62040-2 | |
design and testing:IEC62040-3 |